FlowconSupportTroubleshooting. HW_F1Red

Symptom:

Ingredient Stop (F1 key) is illuminated bright red and you can't permanently reset it. . . it keeps going back on.

Probable Cause (in most likely order)

A scale in overload (weight value varies - check your manual for value).
A scale reading missing or too slow.
Bad scale(s).

Diagnostic:

Compare scale readings to scale maximums.
Compare scale displays to indicated on Flowcon screen.
Run the interrupt mode scale test.

Fix:

Dump overloaded scale from manual panel.
Repair any non-functioning scale (see next 'symptom').
Increase the update rate of any scale measuring a time between readings value greater than 0.25 seconds (i.e. slower than 4 readings / sec).